Service Manual
Models: 400 - 801
This manual must only be used
by a qualified heating installer /
service technician. Read all
instructions, including this manual
and the Knight XL Installation and
Operation Manual, before installing.
Perform steps in the order given.
Failure to comply could result in
severe personal injury, death, or
substantial property damage.
WARNING
Save this manual for future reference.
KBXII-SER Rev F
Vista de página 0
1 2 3 4 5 6 ... 47 48

Resumo do Conteúdo

Página 1 - Service Manual

Service ManualModels: 400 - 801 This manual must only be used by a qualified heating installer / service technician. Read all instructions, includi

Página 2 - Contents

1 Service101 Service General OperationHow the boiler operatesThe Knight XL uses an advanced stainless steel heat exchanger and an electronic control

Página 3 - Please read before proceeding

1 Service1 Service (continued)Table 1-1 Sequence of OperationOPERATION DISPLAY1. Upon a call for heat, the gas pressure switch(es) must be closed.

Página 4

1 Service121 Service Table 1-1 (continued from previous page) Sequence of OperationOPERATION DISPLAY8. If the space heating call for heat is active

Página 5 - What is in this manual?

1 Service131 Service (continued)Display panel menu accessTable 1-2 Use this procedure to access menus from the display panelBUTTONSCREEN STATUSOPERA

Página 6

1 Service141 Service Display panel parameter accessTable 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Set

Página 7

1 Service151 Service (continued)Parameter tableTable 1-4 This table lists SMART SYSTEM control module parameters and where to access them

Página 8

1 Service161 Service Parameter table Service ManualTable 1-4 (continued from previous page) This table lists SMART S

Página 9

1 Service (continued)17Parameter table Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to

Página 10 - 1 Service

181 ServiceViewable and changeable control parameters Service ManualGeneralTime and Date The control uses an internal c

Página 11 - Service1 Service (continued)

191 Service (continued) Service Manual3-Way Valve TimeThe optional Lochinvar Multi-Temperature Loop Control Board (MTLC

Página 12

2Hazard definitionsThe following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or

Página 13 - 1 Service (continued)

201 Service Service ManualFreeze Protection Burner DifferentialOnce the burner has started firing due to a low inlet te

Página 14

1 Service (continued) Service ManualSET POINT ATLOW OUTDOORTEMPERATURE(SH)SET POINTSET POINT ATHIGH OUTDOORTEMPERATUREL

Página 15

1 Service Service ManualBoost Time The boost time parameter sets the amount of time that must elapse with a SH demand b

Página 16

1 Service (continued) Service ManualBMSThe set point or modulation of the boiler may be controlled through the 0 - 10V

Página 17

241 Service Service ManualThe other Cascade divider method is Efficiency Optimization, designated as EFF in the menu.

Página 18

251 Service (continued) Service ManualDHW Blocks Sys PumpWhen the indirect DHW tank is connected as a zone on the prima

Página 19

261 Service Service ManualService Name and Phone NumberWhen a Maintenance Reminder timer or counter has expired, a Main

Página 20

2 Maintenance27Maintenance and annual startupTable 2-1 Service and Maintenance SchedulesService technician(see the following pages for instructions)G

Página 21

2 Maintenance28Follow the Service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Fail

Página 22

2 Maintenance (continued) 29Flue vent system and air piping1. Visually inspect the entire flue gas venting system and air piping for blockage, deter

Página 23

Service Manual Please read before proceedingInstaller – Read all instructions, including this manual and the

Página 24

2 Maintenance30Inspect ignition and flame sense electrodes1. Remove the ignition and flame sense electrodes from the boiler heat exchanger access co

Página 25

2 Maintenance (continued) 31Check flame signal1. At high fire the flame signal shown on the display should be at least 10 microamps.2. A lower flam

Página 26

2 Maintenance 32 Service ManualTest low water flow conditions NOTICEThis test is to be carried out once the Knight XL b

Página 27 - 2 Maintenance

3 Troubleshooting33Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always d

Página 28

3 Troubleshooting 34Table 3-1 Troubleshooting Chart - No Display Service ManualFAULT CAUSE CORRECTIVE ACTIONNo Display-

Página 29 - 2 Maintenance (continued)

3 Troubleshooting (continued)35Table 3-2A - Inlet Water/System Sensor Resistance vs. TemperatureTemperature Resistance Temperature Resistance50 18,78

Página 30

3 Troubleshooting 36Table 3-3 Troubleshooting Chart - Noisy SystemFAULT CAUSE CORRECTIVE ACTIONNoisy Operation- Supply gas problem. Natural gas p

Página 31

3 Troubleshooting (continued)37Table 3-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interface Service M

Página 32

3 Troubleshooting 38Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

Página 33 - 3 Troubleshooting

3 Troubleshooting (continued)39Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

Página 34

4Please read before proceedingWhen servicing boiler –• To avoid electric shock, disconnect electrical supply before performing maintenance.• To avoi

Página 35 - Troubleshooting (continued)

3 Troubleshooting 40Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

Página 36

3 Troubleshooting (continued)41Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

Página 37

3 Troubleshooting 42Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

Página 38

3 Troubleshooting (continued) 43Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface FAULT D

Página 39

3 Troubleshooting44Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface FAULT DESCRIPTION CO

Página 40

3 Troubleshooting (continued) 45Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface FAULT D

Página 41

3 Troubleshooting46 Service ManualCombustion Analysis Procedure1. Turn the main power off to the boiler by placing the

Página 42

473 Troubleshooting (continued)Gas valve adjustment procedureIf adjustment of the gas valve is deemed necessary, use the following procedures: (Note:

Página 43

Revision Notes: Revision A (ECO #C05747) initial release. Reflects the new model numbers for the Knight XL upgrade.Revision B (ECO #C06234) reflects

Página 44

5What is in this manual?ServiceNear boiler piping• Typical system componentsThe Knight XL display• Display panel readout, buttons and their functionsC

Página 45

1 Service6Y-S T R A IN E R(RECOMMENDED)BOILER PUMP INDIRECT DOMESTICHOT WATER TANKSYSTEM PUMPTO FLOOR DRAIN TOFROMFROMSYSTEMTOSYSTEMDOMESTIC HO

Página 46

71 Service (continued)NAVIGATION DIALThe Knight XL displayThe information on the bottom of the display shows the functions of the two SELECT keys (on

Página 47

1 Service81 Service GAS PRESSURE SWITCHDHW THERMOSTATROOM THERMOSTAT /ZONE CONTROLFLOW SWITCHSYSTEM SENSOROUTDOOR SENSORSEQUENCER / BUILDINGMANAGMEN

Página 48

1 Service91 Service (continued)LOW VOLTAGE CONNECTIONBOARDSMART CONTROLMODULEALARM BELLLOUVER RELAYRUN TIME CONTACTSBUILDING MANAGEMENT SYSTEMBOILER